| Product | Type | Capacity | Cooling |
|---|---|---|---|
| Central Chiller | Single-Zone Module | 46.4 Tons | Air-Cooled (Remote) |
-Download Datasheet
-Download Installation & Operation Manual
Advantage literature and installation/operation manual covering the C-50APT-RC (PDF). Note: Unit pictured is representative of standard unit and may not exactly depict p/n C-50APT-RC as shown on this page.
The C-50APT-RC is a 46.4-ton APT-RC chilling module — the refrigeration side only (compressors, evaporator and a remote air-cooled condensing section) with 2×25 HP scroll compressors across 1 refrigerant zone. This is a module, not a self-contained chiller: it has no integral reservoir or process pump, and it's designed to parallel onto a separate pump tank station that circulates fluid through the process loop. Plan for that pump tank station as part of the system, not as an afterthought — its pump curve and reservoir volume are as much a part of sizing this correctly as the module's own tonnage. Remote condensing section: KCL-79-KR, 4-fan.