Advantage MG Series Portable Chillers

1/4 to 40 Tons, Air-Cooled, Water-Cooled or Remote-Condenser

Thirty-eight standard packages covering M1 fractional units through the 40-ton MG frame — one platform, three condenser configurations.

Advantage MG Series portable chiller

MG Series

PRODUCT TYPE CAPACITY COOLING
Portable Chiller Self-Contained 1/4 – 40 Tons Air / Water / Remote

Specifications


Configuration & Size

Capacity:
1/4 – 40 Tons
Cooling:
Air, Water or Remote Condenser
Standard Models:
38
Type:
Portable, Self-Contained
Brand:
Advantage

Construction

  • Compressors: Scroll, Tandem or Digital Scroll
  • Process Pump: Centrifugal or Positive Displacement
  • Pump Body: Stainless Steel or Brass
  • Reservoir: Factory-Insulated Tank

Ratings

  • Fluid Temperature: 20°F – 80°F
  • Design Ambient: 90 – 95°F
  • Refrigerant: R-513A (2 Tons and Under), R-454B (3 Tons and Up)
  • Voltage: 115V to 575V

MG Series Portable Chillers

One Platform, Three Ways to Reject Heat

Advantage's MG platform is the workhorse of the Portable line — thirty-eight standard packages running from a 1/4-ton bench unit (M1-.25A) up to a 40-ton, dual-compressor frame (MG-40W / MG-40ARC), all built the same way: a hermetic or scroll compressor, a factory-plumbed process pump, and a reservoir in one skid or cabinet that only needs power, a process connection and (on water-cooled and remote-condenser models) a water or line-set connection to run. Nothing on this platform is field-assembled from separate components, which is the whole point of a portable chiller — it shows up, gets plumbed in, and starts cooling the same day.

The line splits into three configurations, and picking the wrong one is the single most common sizing mistake we see. Air-cooled units (M1 and MG/MGD-A) reject heat straight to the surrounding air through an integral fan or blower condenser — no tower, no plant water, no drain. They're the default choice below about 10 tons, and above that they're still the right call whenever plant water isn't already piped to the location or isn't free. The trade-off is ambient sensitivity: every air-cooled unit's capacity is rated at a stated ambient (90–95°F on this platform), and a unit that's correctly sized for a 95°F mechanical room will lose real capacity if that room actually runs hotter in August. If your space runs warm, oversize the condenser side or move to water-cooled.

Water-cooled units (MG-W) use city or tower water instead of an air-cooled coil, and they win on two things: a smaller footprint per ton (no condenser coil or fan deck to fit) and a capacity that doesn't fall off in a hot mechanical room, because the water supply temperature does the same job regardless of room ambient. The cost is a running water budget — our 2-ton MG-2W needs roughly 3 GPM on city water or 6 GPM on a tower loop, and that scales up through the line to 60 GPM city / 120 GPM tower on the 40-ton MG-40W. If that water is metered and billed, or if there's no tower already on site, run the numbers before defaulting to water-cooled just because it's compact.

Remote-condenser units (MG-ARC) split the difference: the compressor, pump and reservoir stay indoors in a package the same size as the water-cooled frame, and only the condensing section — fans and coil — sits outside on its own refrigerant line set. This is the right answer when the process floor has no room for condenser airflow, when noise or heat rejection into the space is a problem, or when the equipment room simply has no path to outdoor air but the roof or an exterior wall does. The line set is the detail that gets missed: vertical lift, total equivalent length and the number of elbows all have to be checked against the compressor's charge and oil-return limits before the run is finalized, and that's a conversation to have with us before the unit ships, not after it's installed forty feet from where the compressor sits.

Every MG package on this page uses either a fixed-speed scroll compressor (2 to 4 tons), a digital scroll (5 to 15 tons, modulating for a load that varies through the shift instead of just cycling on and off), or two fixed-speed scrolls run in tandem (15 tons and up, so the unit keeps running at half capacity if one circuit needs service instead of going down completely). None of that changes how the unit is plumbed or wired at the skid level — it only changes how well the unit tracks a load that isn't constant, which is worth knowing before assuming "bigger tonnage" is always the fix for a control problem that's actually a compressor-staging problem.

One more distinction worth making before requesting a quote: the fan-cooled (AF) and blower-cooled (AB) versions of the same tonnage are mechanically identical chillers with a different condenser air path. AF units exhaust straight out the side or top through open propeller fans — fine for an open mechanical room. AB units push that same air through a duct via a blower, which is the version to specify when the unit sits in a tight room and the hot discharge air has to be ducted somewhere else. Getting this wrong doesn't change the chiller's tonnage on paper, but it can mean the difference between a unit that holds its rated capacity and one that's re-breathing its own hot exhaust.



Advantage M1 fractional-ton portable chiller

M1 fractional-ton model shown; the MG platform runs from 1/4 ton up to 40 tons.

Request a Quote

MG Series Applications

Plastics Injection Molding
Plastics Injection Molding
Laser & CNC Machine Cooling
Laser & CNC Machine Cooling
Medical & Lab Equipment
Medical & Lab Equipment
Food & Beverage Spot Cooling
Food & Beverage Spot Cooling

MG portable chiller with built-in reservoir and process pump piped to a machine

Reservoir and Pump Sizing Aren't an Afterthought

Every MG package ships with a factory-matched reservoir and process pump, and it's tempting to treat both as fixed once the tonnage is picked. They aren't. The reservoir has to hold enough fluid volume to buffer the compressor's duty cycle without short-cycling — too small, and the compressor hunts; on this platform reservoir capacity steps from 4 gallons on the smallest M1 units up to 65 gallons on the 15-ton-and-larger frames, sized against the compressor's minimum run time, not just the tonnage.

The process pump is the other half of that equation, and it's picked against your actual GPM and head requirement, not just "whatever ships with that tonnage." A pump that's undersized for your loop's friction loss will starve flow at the process connection even though the compressor is delivering full capacity upstream; oversized, and you're paying for horsepower and generating pump heat the loop doesn't need. Give us the loop's total developed head along with the required flow — not just the flow — and we'll confirm the standard pump curve fits before the unit ships, or spec the next size up. Call and talk it through with an engineer: 1-805-484-2992

Matching an MG model to a job comes down to four numbers: the actual heat load in tons or BTU/hr, the required process fluid temperature, the site ambient (for air-cooled) or the available water GPM (for water-cooled), and the process connection size you're plumbing into. Send us those four and a configuration — air-cooled, water-cooled or remote-condenser — and we'll confirm the model number rather than having you back-calculate it from a catalog.

Still narrowing down the configuration itself? See Air-Cooled vs Water-Cooled and Portable vs Central Chillers, or go straight to Request a Quote with your numbers.

Common FAQs

MG-series units are built for fluid temperatures from 20°F to 80°F. Working pressure is set by the process pump's rated head (typically 30–60 PSI on this platform) rather than a shell pressure rating, since these are packaged pump-and-reservoir units, not pressure vessels.

Air-cooled units need power and a process connection only, plus clearance in front of the condenser coil for airflow. Water-cooled units add a city or tower water supply and drain. Remote-condenser units add a refrigerant line set to the outdoor condensing section, sized for the actual run length before the unit ships.

Condenser coils (air-cooled units) need periodic cleaning to hold rated capacity, and the reservoir strainer and process fluid should be checked on a schedule matching your fluid type. Water-cooled units add periodic condenser-tube inspection for scale, especially on city water without treatment.

From the nameplate model number (M1-, MG- or MGD- prefix followed by tonnage/HP and a configuration suffix -- A for air-cooled, W for water-cooled, ARC for remote-condenser). Send us that number along with the nameplate's electrical data and we can confirm the exact model and specs.

Advantage rates MG capacity at a 50°F leaving fluid temperature, and 48°F is the lowest recommended setpoint on plain water. Below 48°F the loop needs inhibited propylene glycol, mixed so its freeze point sits at least 25°F below the lowest setpoint; a 30% mix freezes at about 0°F. Never use automotive antifreeze, because its silicate inhibitors gel on heat transfer surfaces. Plan for capacity loss as the setpoint drops: available output is 90% of rated at 45°F, 70% at 35°F and 40% at 20°F, so size a cold-loop MG against the derated figure, not the 50°F rating.

The 2 to 40 ton MG models ship with Advantage's MG control instrument: a graphic LCD with plain-language error messages, digital refrigerant and process water pressure readouts, an alarm output with audible signal, and a high water temperature shutdown. Modbus RTU or SPI communication is included and Modbus TCP is optional, so the chiller can report to a press controller or plant system. Capacity control gives 50-100% modulation as standard on 2-40 ton units, and the 5, 7.5 and 10 ton digital scroll units modulate from 20 to 100%. The 1/4 to 1.5 ton M1 units use a simpler LED control with fault and capacity lights.

Use hose or pipe rated for at least 100°F and 70 PSI, no smaller than the chiller's process connections, and keep elbows and run length to a minimum. Put a high-volume basket strainer or bag filter (20-40 micron) with isolation valves in the From Process line; a wye strainer doesn't hold enough debris. If the piping runs overhead, Advantage offers an overhead piping kit that keeps the reservoir from overflowing at shutdown, and a reverse flow circuit for open processes that use an external reservoir. An automatic low flow bypass is available when process flow falls below the evaporator's minimum.

Air-Cooled

Model Tons Compressor HP Pump GPM Process Conn.
M1-.25A 0.29 0.25 0.7 1/2"
M1-.33A 0.39 0.33 0.9 1/2"
M1-.5A 0.5 0.5 1.2 1/2"
M1-.75A 0.75 0.75 1.8 1/2"
M1-1A 1 1 2.4 1/2"
M1-1.5A 1.5 1.5 3.6 1/2"
MG-2A 2 2 4.8 3/4"
MG-3A 2.9 3 7.2 1"
MG-4A 4 4 9.6 1-1/4"
MGD-5A 4.9 5 12 1-1/4"
MGD-7.5A 7.2 7.5 18 1-1/4"
MGD-10A 9.8 10 24 1-1/4"
MG-15AF 14.5 15 36 2"
MG-15AFF 14.5 15 36 2"
MG-15AB 14.5 15 36 2"
MG-20AF 19.3 20 48 2"
MG-20AFF 19.3 20 48 2"
MG-20AB 19.3 20 48 2"
MG-25A 24.5 25 60 2"
MG-30A 29 30 72 2"

Water-Cooled

Model Tons Compressor HP Pump GPM Process Conn.
MG-2W 2 2 4.8 3/4"
MG-3W 3 3 7.2 3/4"
MGD-5W 5.1 5 12 1-1/4"
MG-7.5W 7.6 7.5 19 1-1/4"
MGD-10W 10.6 10 26 1-1/4"
MGD-15W 15 15 36 2"
MG-20W 20 20 48 2"
MG-25W 26 25 60 2"
MG-30W 30 30 72 2"
MG-40W 40 20 92 2-1/2"

Remote-Condenser

Model Tons Compressor HP Pump GPM Process Conn.
MGD-5ARC 4.9 5 12 1-1/4"
MG-7.5ARC 7.1 7.5 19 1-1/4"
MGD-10ARC 9.8 10 26 1-1/4"
MGD-15ARC 14.5 15 36 2"
MG-20ARC 18.5 20 48 2"
MG-25ARC 23.1 25 60 2"
MG-30ARC 30 30 72 2"
MG-40ARC 36.7 20 92 2-1/2"

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Engineering - Sales