Advantage Glycol Chillers

1.5 to 210 HP, Indoor or Outdoor

Advantage glycol chillers for process loops that run below the freeze point of plain water, or that need year-round outdoor freeze protection.

Overview

A glycol chiller is built to circulate a glycol-water solution rather than plain water, so it can deliver fluid temperatures below 32°F and survive outdoor installation through winter without draining down. Advantage's glycol packages run 1.5 to 210 horsepower and are available as indoor units for a mechanical room or outdoor units that sit on a pad year-round.

Both configurations are offered in single-zone (one fluid temperature) and dual-zone (two independent fluid temperatures from one unit) models, which matters most where different parts of a process need different glycol temperatures - product cooling and jacket cooling on the same line, for example.

Glycol changes more than the freeze point: it also carries heat less efficiently than plain water, so a glycol-rated pump, evaporator and piping have to be sized against the actual concentration the process needs, not swapped in on top of a design built for water. That's why these are their own dedicated series rather than a water chiller with glycol poured in afterward - the evaporator surface, pump curve and reservoir on an Advantage BG or BGD unit are all matched to glycol service from the factory.

Configuration Horsepower Range Notes
Indoor Units 1.5 to 210 HP Mechanical-room installation, single or dual zone
Outdoor Units 1.5 to 210 HP Weatherproof, no mechanical room needed, single or dual zone

Which Size Is Right?

Glycol percentage is a selection input, not an afterthought - it sets both the achievable low temperature and the pump/heat-transfer performance of the loop, since glycol solutions carry heat less efficiently than plain water as concentration rises. Tell us the lowest fluid temperature the process actually needs (not the lowest you can imagine wanting) and we'll recommend a percentage rather than defaulting to a round number.

See the Glycol & Low-Temperature Guide under Sizing & Selection for how percentage, freeze point and pump performance interact. Full part-number line-ups for every indoor and outdoor glycol model live on the BG series page; breweries feeding several tanks from one loop should also see the BC-SCC tank control cabinet, which gives each tank its own independent setpoint off a single central glycol chiller.

1.5 to 210 HP

Sub-32°F Capable

Single or Dual Zone

Indoor or Outdoor

What Sets Glycol Cooling Apart

Range

1.5-210 HP


Every Duty Size

From a single NEMA 4 cabinet on one fermenter to a plant-scale unit feeding several process loops at once, without stepping outside the glycol-rated evaporator, pump and piping platform.

Setpoint

Sub-32°F Capable


Below What Water Can Do

Plain water risks freezing inside the chiller's own heat exchanger below roughly 40°F. A properly mixed glycol loop is what gets the process there without that risk - concentration is set from the process's actual required temperature.

Zoning

Single or Dual


One Unit, Two Temperatures

Advantage dual-zone models produce two independent glycol temperatures from a single frame - useful anywhere product cooling and jacket cooling on the same line need different setpoints.

Location

In or Out


Mechanical Room or Pad

Indoor units suit a plant with mechanical-room space; outdoor units are the standard for breweries and distilleries running a year-round exterior loop with no drain-down for winter.

SHOP BY INSTALLATION

Indoor glycol chiller mechanical room installation

Indoor Units

Mechanical-room installation, 1.5 to 210 HP, single or dual zone, rated for glycol service throughout.

Learn More
Outdoor weatherproof glycol chiller on a pad

Outdoor Units

Weatherproof enclosure, no mechanical room, the standard configuration for brewery and distillery glycol loops.

Learn More
BC-SCC brewery tank control cabinet

BC-SCC Tank Control

Gives each tank on a shared glycol loop its own independent setpoint from one central chiller.

Learn More

Glycol Chillers - Frequently Asked Questions

If the process fluid needs to run below roughly 40°F, or the unit will sit outdoors year-round without draining down for winter, glycol is required - plain water risks freezing inside the chiller's own evaporator at those temperatures.

It's set by the lowest leaving fluid temperature the loop has to hit, not a fixed default - a 45°F loop needs far less glycol than a 25°F one. Send us the required setpoint and we'll confirm a percentage rather than defaulting to a round number that either under-protects the loop or wastes pump capacity.

Yes - both indoor and outdoor Advantage glycol units run either food-grade propylene glycol (required near product-contact loops and wash-down areas) or industrial ethylene glycol elsewhere. Tell us which the application requires; the pump and reservoir are sized the same way for both, but the fluid choice matters for anything near a food or beverage process.

No - a dual-zone unit is one frame with two independent refrigerant circuits and controls, not two separate chillers bolted together. It's serviced as one machine, with each zone's controls accessible from the same cabinet.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Engineering - Sales