Advantage APT-RC Series Central Chillers

5 to 180 Tons, Air-Cooled Chilling Modules

Refrigeration-only modules with a remote condenser

Advantage APT-RC chilling module with remote air-cooled condenser

APT-RC Series

PRODUCT TYPE CAPACITY COOLING
Central Chiller Chilling Module 5 – 180 Tons Air-Cooled (Remote)

Specifications


Configuration & Size

Capacity:
5 – 180 Tons
Zones:
Single, Dual or Triple
Standard Models:
22
Condenser:
Remote, Air-Cooled
Brand:
Advantage

Construction

  • Compressors: Scroll
  • Reservoir & Pump: Separate Pump Tank Station
  • Receiver & Oil Separator: Built In
  • Controls: MZC III Multizone

Ratings

  • Fluid Temperature: 20°F – 80°F
  • Refrigerant: R-454B
  • Voltage: 230V / 460V / 575V
  • Three Phase, 60 Hz

APT-RC Series Air-Cooled Chilling Modules

Refrigeration Only, Built to Pair With a Pump Tank Station

Twenty-two refrigeration-only modules with a remote condenser, built to pair with your pump tank station.

APT-RC is Advantage's air-cooled central chilling module line — the refrigeration side only: compressor(s), evaporator and a remote air-cooled condensing section, with no integral reservoir or process pump. That's a deliberate design, not a missing feature. A module is built to parallel onto a pump tank station a plant already has (or specifies alongside it), which makes it the right tool for adding tonnage to an existing chilled-fluid loop rather than replacing a working system just to get more capacity. Twenty-two standard modules cover roughly 5 to 180 tons each, across single-, dual- and triple-zone configurations.

Say this plainly before requesting a quote, because it changes what you're buying: every APT-RC module requires a separate pump tank station to actually circulate fluid through your process. If you don't already have one sized and in place, that's a second line item to plan for and size correctly — reservoir volume, pump head and flow all have to match both the module's evaporator flow requirement and your process loop's actual friction loss, not just the module's tonnage.

Multiple modules can run against the same pump tank station to reach a plant-wide total well beyond what any single packaged chiller carries — the largest single APT-RC module tops out at 180 tons (CCC-180APT-RC), and paralleling modules is how Advantage-equipped plants reach 300 tons and, in custom-engineered combinations, beyond that. Two of these modules are worth flagging by name before you spec off the part number alone: CC-100APT-RC and CCC-150APT-RC publish actual cooling capacities of 90 and 135 tons respectively — the "100" and "150" in their model numbers track total compressor horsepower (4×25 HP and 6×25 HP), not tonnage. Size and quote both units off their real published tonnage, not the number printed in the part number.

Each module's remote condensing section ships on its own refrigerant line set, sized against the compressor's charge and oil-return limits for the actual indoor-to-outdoor run — vertical lift, total equivalent length and elbow count all have to be checked before that run is finalized, which is a conversation to have with us before the module ships, not after it's installed.



Advantage APT-RC chilling module control enclosure with gauges, display and emergency stop

Refrigeration-only chilling modules with a remote air-cooled condenser, sized to parallel onto a pump tank station.

Request a Quote

APT-RC Series Applications

Plastics Injection Molding
Plastics Injection Molding
Plant-Wide Chilled Water Expansion
Plant-Wide Chilled Water Expansion
Machine Tool Cooling
Machine Tool Cooling
Brewery & Beverage Process Cooling
Brewery & Beverage Process Cooling

APT-RC chilling module piped to a separate pump tank station and the process machine

A Module Is Only Half the System

Every APT-RC module ships without a reservoir or process pump, and it's easy to price the module and stop there. Don't. The pump tank station it runs against has to be sized to the module's actual evaporator flow requirement and your process loop's friction loss — not just picked from a catalog by "the tank that looks about right for this tonnage." An undersized pump starves flow at the process connection even with the module delivering full refrigeration capacity upstream; an undersized reservoir lets the loop short-cycle the compressor.

If you're adding a module to an existing pump tank station, send us that station's current pump curve, reservoir volume and how many other modules already run against it. If you're specifying both together, send us the process loop's flow and head requirement along with the tonnage, and we'll size the module and the station as one system rather than two separate guesses.
Call and talk it through with an engineer: 1-805-484-2992

An APT-RC quote covers the station as well as the module: give us the heat load in tons, the process fluid temperature, how many independent zones there are, the flow and head of the pump tank station (existing, or being specified alongside it), and the process connection size. If the loop will run below 48°F, add the glycol concentration, since glycol raises the flow and pump head the station must deliver.

Not sure whether a module-plus-pump-tank system or a self-contained OACS or Titan package is the better fit? See Portable vs Central Chillers, or take your numbers straight to Request a Quote.

Common FAQs

No. APT-RC is refrigeration only - compressor, evaporator and a remote air-cooled condensing section - so every module needs a separate pump tank station to move fluid through your process loop. Carry that station as its own line item when you compare an APT-RC quote with a packaged Titan or OACS price, or the module will look cheaper than the finished system is. Its pump also has to push the module's evaporator flow: moving 90 tons (1,080,000 BTU/hr) at a 10°F rise takes about 216 GPM, from BTU/hr = 500 x GPM x deltaT.

Because its model number counts compressor horsepower, not tons: 4 x 25 HP = 100 HP, while the published, actual cooling capacity is 90 tons. Size and quote this unit off that figure. The same pattern applies to the CCC-150APT-RC (6 x 25 HP = 150 HP, 135 tons actual). Read the labels as tonnage and the error compounds: a plant that adds one of each expecting 250 tons gets 225, a 25-ton gap worth about 300,000 BTU/hr that tends to surface on the hottest production week of the year.

Yes - multiple modules can parallel onto the same station to reach a total larger than any single packaged chiller in the range. Send us the station's existing pump curve and reservoir volume along with the additional tonnage you need. What usually runs out first is the station rather than refrigeration: each module adds evaporator flow the pump must deliver on top of process demand, and a reservoir that suited one module can let compressors short-cycle once two or three are staging against it.

Where the heat goes. APT-RC modules are air-cooled, with a remote condensing section on its own line set; WPT modules are water-cooled, rejecting heat to condenser water instead, with no remote condenser or outdoor footprint. Both require a separate pump tank station. The building usually settles it: tower water already piped to the room favors WPT, while no tower favors APT-RC and spares the plant a water treatment program. Remember that air-cooled capacity falls as outdoor temperature climbs, whereas WPT capacity follows the condenser water temperature instead.

Through two connections, both piped rigidly to the station. Process Water In receives the warm return water the station sends back from the process; Process Water Out goes to the chilled side of the station's reservoir, and the station's pump supplies the process. Land the outlet on the warm side by mistake and the module mostly recools its own water while the process runs warm. On the incoming line, fit isolation valves and a large-capacity basket strainer or bag filter of 40 mesh (about 400 micron) or finer; wye strainers don't hold enough debris. Use piping rated to at least 100°F and 100 PSI, no smaller than the connections, insulated against condensation and capacity loss.

Everything between the module and its remote condenser; the receiver and oil separator are built into every Advantage APT-RC module, so they are not seperate field items. The piping is refrigerant-grade copper joined with high-temperature phos-copper, never soft solder or water pipe. The installer adds discharge line check valves after the oil separator, shut-off valves in the hot gas and liquid lines, inverted traps, and relief valves plus recovery ports at the condenser, and secures the lines near the coil on runs longer than 50 ft. A certified refrigeration technician then evacuates and charges the system under load, so book that contractor when the module is ordered.

Yes. Each module runs on the MZC III multizone instrument with one intelligent zone board per refrigeration circuit, and those boards can connect to a Titan's display board, so the added tonnage runs in paralell as part of the same system. One instrument handles up to six refrigeration circuits - count them before ordering, since three existing circuits plus one triple-circuit module already fill it. On dual and triple circuit modules each circuit runs independently, giving finer capacity staging and letting the others keep cooling while one is down. Modbus RTU or SPI is standard; Modbus TCP and a remote display are options.

Single-Zone

Model Tons Type Cooling
C-5APT-RC 5 Central Chilling Module, Single Zone Air-Cooled (Remote)
C-7.5APT-RC 9.1 Central Chilling Module, Single Zone Air-Cooled (Remote)
C-10APT-RC 11.5 Central Chilling Module, Single Zone Air-Cooled (Remote)
C-15APT-RC 15 Central Chilling Module, Single Zone Air-Cooled (Remote)
C-20APT-RC 19 Central Chilling Module, Single Zone Air-Cooled (Remote)
C-25APT-RC 25 Central Chilling Module, Single Zone Air-Cooled (Remote)
C-30APT-RC 30 Central Chilling Module, Single Zone Air-Cooled (Remote)
C-40APT-RC 36.7 Central Chilling Module, Single Zone Air-Cooled (Remote)
C-50APT-RC 46.4 Central Chilling Module, Single Zone Air-Cooled (Remote)
C-60APT-RC 60 Central Chilling Module, Single Zone Air-Cooled (Remote)

Dual-Zone

Model Tons Type Cooling
CC-20APT-RC 23 Central Chilling Module, Dual Zone Air-Cooled (Remote)
CC-30APT-RC 30 Central Chilling Module, Dual Zone Air-Cooled (Remote)
CC-40APT-RC 38 Central Chilling Module, Dual Zone Air-Cooled (Remote)
CC-50APT-RC 50 Central Chilling Module, Dual Zone Air-Cooled (Remote)
CC-60APT-RC 60 Central Chilling Module, Dual Zone Air-Cooled (Remote)
CC-80APT-RC 80 Central Chilling Module, Dual Zone Air-Cooled (Remote)
CC-100APT-RC 90 Central Chilling Module, Dual Zone Air-Cooled (Remote)
CC-120APT-RC 120 Central Chilling Module, Dual Zone Air-Cooled (Remote)

Triple-Zone

Model Tons Type Cooling
CCC-90APT-RC 90 Central Chilling Module, Triple Zone Air-Cooled (Remote)
CCC-120APT-RC 120 Central Chilling Module, Triple Zone Air-Cooled (Remote)
CCC-150APT-RC 135 Central Chilling Module, Triple Zone Air-Cooled (Remote)
CCC-180APT-RC 180 Central Chilling Module, Triple Zone Air-Cooled (Remote)