OACS-100D-MZC-2P-BC

Advantage Engineering
Product Type Capacity Cooling
Glycol Chiller Outdoor Dual-Zone 654,000 BTU/hr @ 25°F Air-Cooled
PDF -Download Datasheet

Advantage literature covering the OACS-100D-MZC-2P-BC (PDF). Installation/operation manual on request - call or email. Note: Unit pictured is representative of standard unit and may not exactly depict p/n OACS-100D-MZC-2P-BC as shown on this page.

OACS-100D-MZC-2P-BC glycol chiller

Description

The OACS-100D-MZC-2P-BC adapts Advantage's OACS outdoor central chiller platform for glycol duty, not a straight relabel of the standalone water OACS chiller in the same tonnage class — the OACS-100D-MZC-2P-BC ships configured to hold a 25-30°F leaving fluid temperature on a water-and-glycol mixture, and every wetted surface, the reservoir, pump seals and controls setpoints are matched to that duty rather than plain chilled water. It uses a tandem scroll compressor on HFC-410A refrigerant. Compressor is rated at 50 HP. Standard glycol duty holds 654,000 BTU/hr of cooling capacity at a 25°F leaving fluid temperature, and every OACS-series model is adjustable from 20°F up to 70°F as the process requires. The process pump moves 240 GPM, backed by a 400-gallon reservoir. Without glycol in the loop, treat 48°F as the practical minimum leaving fluid temperature for the OACS-100D-MZC-2P-BC — run it colder than that and you need glycol in the system, which is the entire reason this line exists rather than a plain-water MG or Titan unit.

Product Overview

Part Number:
OACS-100D-MZC-2P-BC
Series:
BG
Brand:
Advantage Engineering

Configuration & Specifications

Compressor HP:
50 HP
Compressor Type:
Tandem Scroll
Refrigerant:
HFC-410A
Cooling Capacity @ 25°F:
654,000 BTU/hr
Cooling Capacity @ 50°F:
1,124,400 BTU/hr
Min. Fluid Temp (No Glycol):
48°F
Target Operating Range:
25-30°F
Adjustable Fluid Temp Range:
20-70°F

Pump, Reservoir & Connections

Process Pump HP:
15 HP
Process Pump Flow:
240 GPM
Evaporator Pump HP:
7.5 HP
Evaporator Pump Flow:
240 GPM
Reservoir Capacity:
400 gal
Reservoir Construction:
Polyethylene
Process Connection:
4"

Electrical

  • Voltage: 230V / 460V / 575V
  • Phase: Three Phase
  • Frequency: 60 Hz
  • Full Load Amps (230V): 570.6
  • Full Load Amps (460V): 260.8
  • Full Load Amps (575V): 210.0

Dimensions & Weight

  • Shipping: 9,755 lbs
  • H x W x D: 82" x 88" x 246"

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Engineering - Sales