OACS-30S-MG-1P-BC

Advantage Engineering
Product Type Capacity Cooling
Glycol Chiller Outdoor Single-Zone 197,456 BTU/hr @ 25°F Air-Cooled
PDF -Download Datasheet -Download Installation & Operation Manual

Advantage literature and installation/operation manual covering the OACS-30S-MG-1P-BC (PDF). Note: Unit pictured is representative of standard unit and may not exactly depict p/n OACS-30S-MG-1P-BC as shown on this page.

OACS-30S-MG-1P-BC glycol chiller

Description

The OACS-30S-MG-1P-BC adapts Advantage's OACS outdoor central chiller platform for glycol duty, not a straight relabel of the standalone water OACS chiller in the same tonnage class — the OACS-30S-MG-1P-BC ships configured to hold a 25-30°F leaving fluid temperature on a water-and-glycol mixture, and every wetted surface, the reservoir, pump seals and controls setpoints are matched to that duty rather than plain chilled water. It uses a single scroll compressor on HFC-410A refrigerant. Compressor is rated at 30 HP. Standard glycol duty holds 197,456 BTU/hr of cooling capacity at a 25°F leaving fluid temperature, and every OACS-series model is adjustable from 20°F up to 70°F as the process requires. The process pump moves 72 GPM, backed by a 100-gallon reservoir. Without glycol in the loop, treat 48°F as the practical minimum leaving fluid temperature for the OACS-30S-MG-1P-BC — run it colder than that and you need glycol in the system, which is the entire reason this line exists rather than a plain-water MG or Titan unit.

Product Overview

Part Number:
OACS-30S-MG-1P-BC
Series:
BG
Brand:
Advantage Engineering

Configuration & Specifications

Compressor HP:
30 HP
Compressor Type:
Single Scroll
Refrigerant:
HFC-410A
Evaporator Type:
Brazed plate, stainless steel plates
Cooling Capacity @ 25°F:
197,456 BTU/hr
Cooling Capacity @ 50°F:
360,000 BTU/hr
Min. Fluid Temp (No Glycol):
48°F
Standard Operating Range:
25-30°F
Adjustable Fluid Temp Range:
20-70°F

Pump, Reservoir & Connections

Process Pump HP:
5 HP
Process Pump Flow:
72 GPM
Reservoir Capacity:
100 gal
Reservoir Construction:
Non-ferrous polyethylene
Process Connection:
3"

Electrical

  • Voltage: 230V / 460V / 575V
  • Phase: Three Phase
  • Frequency: 60 Hz
  • Full Load Amps (230V): 167.3
  • Full Load Amps (460V): 82.3
  • Full Load Amps (575V): 66.3

Dimensions & Weight

  • Shipping: 3,785 lbs
  • H x W x D: 91" x 54" x 200"

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Engineering - Sales