| Product | Type | Capacity | Cooling |
|---|---|---|---|
| Central Chiller | Outdoor Dual-Zone | 57.4 Tons | Air-Cooled |
-Download Datasheet
Advantage literature covering the OACS-60D-MZC-2P (PDF). Installation/operation manual on request - call or email. Note: Unit pictured is representative of standard unit and may not exactly depict p/n OACS-60D-MZC-2P as shown on this page.
The OACS-60D-MZC-2P is a dual-zone outdoor air-cooled central chiller producing two independently controlled fluid temperatures from one weatherproof frame — tandem scroll compressors on 2 independent refrigerant circuits, staged and controlled through an MZC multizone controller with independent zone boards. Published capacity is 57.4 tons total (57.4 tons per zone as sourced). The process pump moves 144 GPM at 60 PSI, backed by a 400-gallon polyethylene reservoir, and a standby pump is optional for plants that can't tolerate downtime for a pump service call. Rated for 20°F to 70°F fluid temperatures and an ambient range of -20°F to 95°F.