| Product | Type | Capacity | Cooling |
|---|---|---|---|
| Central Chiller | Indoor | 50 Tons | Air-Cooled |
-Download Datasheet
-Download Installation & Operation Manual
Advantage literature and installation/operation manual covering the TI-50A (PDF). Note: Unit pictured is representative of standard unit and may not exactly depict p/n TI-50A as shown on this page.
The TI-50A is a 50-ton, air-cooled Titan central chiller — a full mechanical-room package with the compressors, evaporator, reservoir and process pump on one frame, using 2×25 HP scroll compressors across 2 refrigerant zones. The process pump moves 120 GPM at 60 PSI, and the reservoir carries 340 gallons of operating fluid volume — plenty of buffer to keep the compressor from short-cycling under a shift's normal load swing. Heat rejects through a remote air-cooled condensing section (KCL-74-KR) on its own refrigerant line set rather than a condenser built into the main cabinet — the compressor package sits in the mechanical room and only the condenser fans and coil go outside or on the roof, which is the point of the Titan indoor-air-cooled configuration. Charged with R-454B.