| Product | Type | Capacity | Cooling |
|---|---|---|---|
| Central Chiller | Indoor | 150 Tons | Water-Cooled |
-Download Datasheet
-Download Installation & Operation Manual
Advantage literature and installation/operation manual covering the TI-150W (PDF). Note: Unit pictured is representative of standard unit and may not exactly depict p/n TI-150W as shown on this page.
The TI-150W is a 150-ton, water-cooled Titan central chiller — a full mechanical-room package with the compressors, evaporator, reservoir and process pump on one frame, using 6×25 HP scroll compressors across 3 refrigerant zones. The process pump moves 420 GPM at 55 PSI, and the reservoir carries 1200 gallons of operating fluid volume — plenty of buffer to keep the compressor from short-cycling under a shift's normal load swing. Heat rejects to city or tower condenser water rather than an air-cooled coil, which is the reason to pick this frame over the equivalent air-cooled Titan model whenever plant water is already piped to the mechanical room and isn't metered at a cost that changes the economics. Charged with R-454B.