| Product | Type | Capacity | Cooling |
|---|---|---|---|
| Glycol Chiller | Indoor | 9,360 BTU/hr @ 25°F | Air-Cooled |
-Download Datasheet
-Download Installation & Operation Manual
Advantage literature and installation/operation manual covering the BC-1.5A (PDF). Note: Unit pictured is representative of standard unit and may not exactly depict p/n BC-1.5A as shown on this page.
The BC-1.5A is an indoor, self-contained glycol chiller — scroll compressor, glycol-rated evaporator and reservoir, and a factory-matched process pump on one frame, sized for a mechanical-room installation. Compressor is rated at 1.5 HP. Standard glycol duty holds 9,360 BTU/hr of cooling capacity at a 25°F leaving fluid temperature, and every BC-series model is adjustable from 20°F up to 70°F as the process requires. The process pump moves 3.6 GPM, backed by a 6-gallon reservoir. Without glycol in the loop, treat 48°F as the practical minimum leaving fluid temperature for the BC-1.5A — run it colder than that and you need glycol in the system, which is the entire reason this line exists rather than a plain-water MG or Titan unit.