BC-1A

Advantage Engineering
Product Type Capacity Cooling
Glycol Chiller Indoor 6,840 BTU/hr @ 25°F Air-Cooled
PDF -Download Datasheet -Download Installation & Operation Manual

Advantage literature and installation/operation manual covering the BC-1A (PDF). Note: Unit pictured is representative of standard unit and may not exactly depict p/n BC-1A as shown on this page.

BC-1A glycol chiller

Description

The BC-1A is an indoor, self-contained glycol chiller — scroll compressor, glycol-rated evaporator and reservoir, and a factory-matched process pump on one frame, sized for a mechanical-room installation. Compressor is rated at 1 HP. Standard glycol duty holds 6,840 BTU/hr of cooling capacity at a 25°F leaving fluid temperature, and every BC-series model is adjustable from 20°F up to 70°F as the process requires. The process pump moves 2.4 GPM, backed by a 6-gallon reservoir. Without glycol in the loop, treat 48°F as the practical minimum leaving fluid temperature for the BC-1A — run it colder than that and you need glycol in the system, which is the entire reason this line exists rather than a plain-water MG or Titan unit.

Product Overview

Part Number:
BC-1A
Series:
BG
Brand:
Advantage Engineering

Configuration & Specifications

Compressor HP:
1 HP
Compressor Type:
Scroll
Refrigerant:
R-513A
Cooling Capacity @ 25°F:
6,840 BTU/hr
Cooling Capacity @ 50°F:
10,680 BTU/hr
Min. Fluid Temp (No Glycol):
48°F

Pump, Reservoir & Connections

Process Pump HP:
1/2 HP
Process Pump Flow:
2.4 GPM
Reservoir Capacity:
6 gal
Process Connection:
1/2" NPT

Electrical

  • Voltage: 230V
  • Phase: Single Phase
  • Frequency: 60 Hz
  • Full Load Amps: 13

Dimensions & Weight

  • Shipping: 345 lbs
  • H x W x D: 38.5" x 24" x 29"

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Engineering - Sales